ESP Fireline 4 zone fire Alarm Panel MAG4P Features - 4 programmable zones
- Activate end of line monitoring
- 30 fire detectors per zone
- Unlimited number of call points per zone
- Integral manual alarm button
- Class change facility
- Enable/disable security key
- One man walk test facility
- Fire volt free change over relay
- Fault volt free change over relay
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- BS5839 and EN54 compliant
- CE certified
- Requires only 1x12v battery (See associated products)
- Polycarbonate case
Technical specifications | INPUTS | Max detectors per zone | 30 | | | Thresholds for zone conditions | 0-2 mA (Fault condition) 2-6 mA (Normal condition) 6-110 mA (Fire condition) 110 mA Short (Short condition) | | POWER | Mains fail consumption | 50mA | | | Mains Supply | 230 VAC ± 10% | | | Standby supply | 1 x 7ah 12V S.L.A. Battery | | | Power availability | 0.7 amps | | OUTPUTS | Sounder 1 | 24V (max 300mA fused) | | | Sounder 2 | 24V (max 300mA fused) | | | Fault Relay | Volt free 500mA (maximum load) | | | Auxiliary output | 24VDC (300mA fused) | | ENVIRONMENT | Working Temperature | 0 to 40°C | | | Storage Temperature | -20 to 60°C | | | Humidity | 0-95% | | | Dimensions (mm) | 340W 290H 100D | | | Weight | 2.5 KG |
Check the compatible alarms and dectectors from ESP in the detectors, call points and alarms catagory.
|